AutomtrJ Interface

Schematic showing the Automtr interface connected to the North Object Model The AutomtrJ interface links a network of Autometers IC Series power meters to North's Extensible Object Model. Meters should be fitted with the optional Modbus communications cassette. Several power meters can be accessed from a single interface module.

Information available from each Autometers power meter includes phase (voltage, current, power factor, frequency), maximum demand (current, power) and total system readings.

Supported Range

Autometers IC2200/1200 Power Meter - Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Phase Frequency, Max Demand KW, Total KWH.
Autometers IC2500/1500 Power Meter - Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Phase Frequency, Phase Power Factor, Instantaneous KW, Max Demand KW, Total KWH.
Autometers IC2700/1700 Power Meter - Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Phase Frequency, Phase Power Factor, Instantaneous KW KVA KVAR, Max Demand KW KVA KVAR, Total KWH KVAH KVARH.
Autometers IC2400/1400 Power Meter - Phase to Phase Voltage, Phase Current and total, Phase Frequency, System Frequency, Instantaneous KW, Max Demand KW, Total KWH.
Autometers IC2600/1600 Power Meter - Phase to Phase Voltage, Phase Current and total, Phase Frequency, System Frequency, Instantaneous KW KVA KVAR, Max Demand KW KVA KVAR, Total KWH KVAH KVARH.
Autometers IC810/810r Power Meter - KWH/KVARH with Pulse Output.
Autometers IC815 Power Meter - Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Power Factor, Frequency.
Autometers IC820 Power Meter - Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Frequency, KWH with Pulse Output, Max Demand KW.
Autometers IC850 Power Meter - Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Power Factor, Frequency, Instantaneous KW, KWH with Pulse Output, Max Demand KW, Total KWH.
Autometers IC870 Power Meter - Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Power Factor, Frequency, Instantaneous KW KVA KVAR, KWH with Pulse Output, Max Demand KW KVA KVAR, Total KWH KVAH KVARH.
Autometers IC890 Power Meter – Harmonic Analysis, THD Voltage Voltage per Phase, THD Current Current per Phase and Neutral, Phase to Neutral Voltage, Phase to Phase Voltage, Phase Current and total, Power Factor, Frequency, Instantaneous KW KVA KVAR, KWH with Pulse Output, Max Demand KW KVA KVAR, Total KWH KVAH KVARH.

Platforms

The Automtrj interface is available on the following North platforms:

Product Codes

CP/AUTOMTRJ/485Compass Point with Automtrj interface
CMDR/AUTOMTRJCompass Point with Automtrj interface1
OSM/AUTOMTRJOSM available with all ObSys editions1

Notes 1 Requires a RS485/232 converter for the interface.